Detailed Specifications & Technical Data METRIC MEASUREMENT VERSION 5320FJ Multi-Conductor - Commercial Applications, Addressable Systems - 2 Cond Cabled For more Information please call 1-800-Belden1 General Description: Fire Alarm Cable, Rated-FPL, 2-18 AWG solid bare copper conductors with foamed polyolefin insulation, Overall Beldfoil(R) shield, PVC jacket with ripcord Usage (Overall) Suitable Applications: Addressable Fire Systems, Data Circuits, Audio Circuits, Control Circuits, Initiating Circuits, Notification Circuits Physical Characteristics (Overall) Conductor AWG: # Conductors AWG Stranding Conductor Material 2 18 Solid BC - Bare Copper Total Number of Conductors: 2 Insulation Insulation Material: Insulation Trade Name Insulation Material Datalene(R) Wall Thickness (mm) FHDPE - Foam High Density Polyethylene 0.381 Outer Shield Outer Shield Material: Outer Shield Trade Name Type Outer Shield Material Beldfoil(R) Coverage (%) Tape Aluminum Foil-Polyester Tape w/Shorting Fold 100 Outer Shield Drain Wire AWG: AWG Stranding Drain Wire Conductor Material 24 Solid TC - Tinned Copper Outer Jacket Outer Jacket Material: Outer Jacket Material Nom. Wall Thickness (mm) PVC - Polyvinyl Chloride 0.8382 Outer Jacket Ripcord: Yes Overall Cable Overall Cabling Lay Length & Direction: Length (mm) Twists (twist/m) 50.7998 19.686 Overall Cabling Color Code Chart: Number Color 1 Black 2 Red Overall Nominal Diameter: 5.359 mm Mechanical Characteristics (Overall) Operating Temperature Range: -20C To +75C UL Temperature Rating: 75C Bulk Cable Weight: 35.717 Kg/Km Max. Recommended Pulling Tension: 192.162 N Min. Bend Radius/Minor Axis: 50.800 mm Applicable Specifications and Agency Compliance (Overall) Applicable Standards & Environmental Programs NEC/(UL) Specification: FPL NEC Articles: 760 Page 1 of 2 01-09-2015 Detailed Specifications & Technical Data METRIC MEASUREMENT VERSION 5320FJ Multi-Conductor - Commercial Applications, Addressable Systems - 2 Cond Cabled EU Directive 2011/65/EU (ROHS II): Yes EU CE Mark: Yes EU Directive 2000/53/EC (ELV): Yes EU Directive 2002/95/EC (RoHS): Yes EU RoHS Compliance Date (mm/dd/yyyy): 01/01/2004 EU Directive 2002/96/EC (WEEE): Yes EU Directive 2003/11/EC (BFR): Yes CA Prop 65 (CJ for Wire & Cable): Yes MII Order #39 (China RoHS): Yes Flame Test UL Flame Test: UL1685 UL Loading Plenum/Non-Plenum Plenum (Y/N): No Plenum Number: 6320FJ Electrical Characteristics (Overall) Nom. Inductance: Inductance (H/m) 0.59058 Nom. Capacitance Conductor to Conductor: Capacitance (pF/m) 86.9465 Nom. Capacitance Cond. to Other Conductor & Shield: Capacitance (pF/m) 155.848 Nom. Conductor DC Resistance: DCR @ 20C (Ohm/km) 20.9984 Nominal Outer Shield DC Resistance: DCR @ 20C (Ohm/km) 58.730 Max. Operating Voltage - UL: Voltage 300 V RMS Max. Recommended Current: Current 5 Amps per conductor @ 25C Put Ups and Colors: Item # Putup Ship Weight Color 5320FJ 002U1000 1,000 FT 27.000 LB RED 5320FJ 0021000 1,000 FT 28.000 LB RED Notes Item Desc 2 #18 FPE FS PVC C 2 #18 FPE FS PVC Notes: C = CRATE REEL PUT-UP. Revision Number: 2 Revision Date: 08-06-2013 (c) 2015 Belden, Inc All Rights Reserved. Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not ensure product availability. Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein. All sales of Belden products are subject to Belden's standard terms and conditions of sale. Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities and in our Distributor's inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden's knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the product. Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC. Page 2 of 2 01-09-2015